Bộ điều khiển đốt RM7800

Thông tin mô tả

7800 SERIES PROGRAMMER CONTROL

"Gọi 0974400989 để được tư vấn miễn phí"

AME

Cam kết hàng mới 100%
Bảo hành chính hãng

A. GENERAL
A.1 OVERVIEW The contractor shall furnish, install, and place in operating condition a Programmer Control as described herein. The system shall be located in accordance with these specifications.
A.2 TYPE OF SYSTEM
A.2.1 Major functions of the Programmer Control shall provide: a. Automatic sequencing of the burner system through Initiation, Standby, Prepurge, Pilot Flame
Establishing Period, Main Flame Establishing Period, Run, and Postpurge.
b. Flame proving and lockout on flame failure during pilot flame proving, main flame proving, or run.
c. Low fire firing rate motor position for flame ignition trials.
d. Modulating switching control of fuel and combustion air.
e. Status light emitting diodes (LEDs) indicating:
       • Power present, green.
       • Main valve energized, yellow.
       • Alarm, red.
       • Pilot valve, yellow.
       • Flame present, red.
f. NEMA 1 rated enclosure.
g. Line voltage terminal inputs for lockout, preignition, and recycle limits and interlocks.
h. Separate annunciation faults including Programmer Control, flame failure, preignition interlocks,lockout interlocks and firing rate interlocks.
i. Self-test for proper operation.
j. Monitor system circuit status.
k. Tamper resistant safety logic and timing.
l. First-out annunciation and diagnostics including display of flame signal, total burner cycles, burner
hours, fault history of last six lockouts, and diagnostic voltage tests of burner I/O via a vacuum fluorescent display (VFD). The VFD shall be able to be mounted remotely within 1000 feet of the Programmer Control.
m. Nonvolatile lockout and history files.
n. Dynamic ampli-check flame amplification protection.
o. Dynamic self-check flame amplification protection.
p. Characterization to the applied burner.
q. Capability for remote or local communication to a personal computer.
r. Ability to be installed in a continuous 0.5G environment.
s. Run/test switch to pause the burner sequence in prepurge and pilot ignition trials to support startuptesting and burner adjustments. 
t. Remote resetting of safety lockouts via a momentary pushbutton. Remote reset switch can be placed up to 1000 feet from the Programmer Control. 
u. High fire firing rate motor position for purge trials.
A.2.2 Major System Components
a. Relay Module
• RM7800M, RM7840M               On-off
• RM7800G, RM7840G               Modulation
• RM7800E/L, RM7840E/L         Modulation with proven high fire
b. Keyboard and Display Module, S7800
c. Flame Amplifier
• Ultraviolet, R7849 A/B, R7886A
• Infrared, R7848A/B • Rectification, R7847A/B/C
d. Flame Sensor
• Ultraviolet, C7012, C7027, C7035, C7076
• Infrared, C7015
• Rectifying flame rod/photocell
e. Mounting Subbase
• Q7800A/B
f. Prepurge Timing Module
• ST7800A
Standard application for Burner or Boiler System:
For more information, please feel free contact us follow hotline 0974400989 or email: hoangtan.ame@gmail.com
 

Tin tức nổi bật

Top